InfraWin 5 Manual Data format UPP® (Universal Pyrometer Protocol) 30
Description Command Parameters
Limit contact 1: AAs1XXXX XXXX = switch point limit contact 1
(ASCII-hex, 4 digit, full degree in °C or °F)
Limit contact 2: AAs2XXXX XXXX = switch point limit contact 2
(ASCII-hex, 4 digit, full degree in °C or °F)
Setting hysteresis of limit
contacts:
AAhlXX XX = 2 … 20, full degree in °C or °F
Changing °C / °F AAfhX *
Output: X = 0: display in °C; X = 1: display in °F
Interface type: AAin Output: X = 1 or 2; 1 = RS232, 2 = RS485
Changing address: AAgaXX *
XX = (00 ... 97)
00 ... 97 = regular device addresses
99 = Global address with response
98 = Global address without response (only setting commands!)
Changing baud rate: AAbrX *
X=0...6 or 8 (dez.)
0 = 1200 baud 3 = 9600 baud 6 = 57600 baud
1 = 2400 baud 4 = 19200 baud (7 is not allowed)
2 = 4800 baud 5 = 38400 baud 8 = 115200 baud
Wait time: AAtwXX *
XX = 00 ... 99 (decimal)
Error status: AAfs Output 1 byte hex (00 = no error)
Bit 0 = 1: Measurement unit doesn’t work
Bit 1 = 1: Internal temperature measurement doesn’t work
Lock keyboard: AAlkX X = 0 ... 3
1 = lock lk1, removal with command lk0 or power off-on
0 = removal of lock lk1
3 = continuous lock lk3, removal only with command lk2
2 = removal of lock lk3
Reading parameters: AApa Output decimal 11-digit:
Digit 1 und 2 (10...99 or 00): e
Digit 3 (0 ... 6): t
90
(Exposition time)
Digit 4 (0 ... 8): t
CL
(max. storage clear mode)
Digit 5 (0 ... 1): Analog output
Digit 6 und 7: (00 ... 98): Temperature
Digit 8 und 9 (00 ... 97): Address
Digit 10 (0 ... 6 or 8): Baud rate
Digit 11 (0): always 0
Laser targeting light: AAlaX *
X = 0 switch off laser
X = 1 switch on laser
Internal temperature: AAgt Output: XX (dez. 00 ... 98, in °C)
XXX (dez. 032 ... 208°F)
Max. internal
temperature:
AAtm Output: XX (dez. 00 ... 98, in °C)
XXX (dez. 032 ... 208°F)
Ref. number: AAbn Output: XXXXXX (hex 6-digit)
Serial number: AAsn Output: XXXX (hex 4-digit)
Device type: AAna Output: “IS 12-Al” or “IS 12-Al/S” (16 ASCII-characters)
Device type /
software version:
AAve Output: XXYYZZ (6-digit decimal)
XX = 07 (IS 12-Al and S 12-AL/S)
YY = Month of software version
ZZ = Year of software version
Software version in detail: AAvs tt.mm.yy XX.YY
tt = Day; mm = month; yy = year; XX.YY = software version
Note: the letter ”l” means the small type of “L”